Filtered by vendor Schneider-electric
                        
                        Subscribe
                        
                        
                    
                    
                
                        Filtered by product Triconex Tricon Mp 3008 Firmware
                        
                        Subscribe
                        
                        
                    
                    
                
                    Total
                    2 CVE
                
            | CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 | 
|---|---|---|---|---|---|
| CVE-2018-8872 | 1 Schneider-electric | 2 Triconex Tricon Mp 3008, Triconex Tricon Mp 3008 Firmware | 2024-11-21 | 9.3 HIGH | 8.1 HIGH | 
| In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory. | |||||
| CVE-2018-7522 | 1 Schneider-electric | 2 Triconex Tricon Mp 3008, Triconex Tricon Mp 3008 Firmware | 2024-11-21 | 7.2 HIGH | 6.7 MEDIUM | 
| In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states. | |||||