CVE-2020-7536 | 1 Schneider-electric | 20 Bmxnoe0100, Bmxnoe0100 Firmware, Bmxnoe0110 and 17 more | 2024-11-21 | 7.8 HIGH | 7.5 HIGH |
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP. | |||||
CVE-2020-7535 | 1 Schneider-electric | 42 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 39 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP. | |||||
CVE-2020-7534 | 1 Schneider-electric | 20 140cpu65, 140cpu65 Firmware, 140noc78000 and 17 more | 2024-11-21 | 6.8 MEDIUM | 8.8 HIGH |
A CWE-352: Cross-Site Request Forgery (CSRF) vulnerability exists on the web server used, that could cause a leak of sensitive data or unauthorized actions on the web server during the time the user is logged in. Affected Products: Modicon M340 CPUs: BMXP34 (All Versions), Modicon Quantum CPUs with integrated Ethernet (Copro): 140CPU65 (All Versions), Modicon Premium CPUs with integrated Ethernet (Copro): TSXP57 (All Versions), Modicon M340 ethernet modules: (BMXNOC0401, BMXNOE01, BMXNOR0200H) (All Versions), Modicon Quantum and Premium factory cast communication modules: (140NOE77111, 140NOC78*00, TSXETY5103, TSXETY4103) (All Versions) | |||||
CVE-2019-6855 | 1 Schneider-electric | 44 Ecostruxure Control Expert, Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware and 41 more | 2024-11-21 | 7.5 HIGH | 7.3 HIGH |
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers. | |||||
CVE-2018-7762 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. | |||||
CVE-2018-7761 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution. | |||||
CVE-2018-7760 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization. | |||||
CVE-2018-7759 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied. | |||||
CVE-2018-7242 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. | |||||
CVE-2018-7241 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2024-11-21 | 10.0 HIGH | 9.8 CRITICAL |
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. | |||||
CVE-2015-6462 | 1 Schneider-electric | 22 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 19 more | 2024-11-21 | 3.5 LOW | 5.4 MEDIUM |
Reflected Cross-Site Scripting (nonpersistent) allows an attacker to craft a specific URL, which contains Java script that will be executed on the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC client browser. | |||||
CVE-2015-6461 | 1 Schneider-electric | 22 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 19 more | 2024-11-21 | 5.5 MEDIUM | 5.4 MEDIUM |
Remote file inclusion allows an attacker to craft a specific URL referencing the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC web server, which, when launched, will result in the browser redirecting to a remote file via a Java script loaded with the web page. |