CVE-2020-14516 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 7.5 HIGH 10.0 CRITICAL
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.
CVE-2020-13573 1 Rockwellautomation 1 Rslinx 2024-11-21 5.0 MEDIUM 7.5 HIGH
A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability.
CVE-2020-12038 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2024-11-21 4.3 MEDIUM 5.5 MEDIUM
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.
CVE-2020-12034 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2024-11-21 4.8 MEDIUM 8.2 HIGH
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions.
CVE-2020-12033 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 5.8 MEDIUM 8.8 HIGH
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
CVE-2020-12031 1 Rockwellautomation 1 Factorytalk View 2024-11-21 4.6 MEDIUM 7.5 HIGH
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2020-12029 1 Rockwellautomation 1 Factorytalk View 2024-11-21 6.8 MEDIUM 9.0 CRITICAL
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2020-12028 1 Rockwellautomation 1 Factorytalk View 2024-11-21 5.5 MEDIUM 7.3 HIGH
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12027 1 Rockwellautomation 1 Factorytalk View 2024-11-21 4.0 MEDIUM 4.3 MEDIUM
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12025 1 Rockwellautomation 1 Studio 5000 Logix Designer 2024-11-21 4.3 MEDIUM 3.3 LOW
Rockwell Automation Logix Designer Studio 5000 Versions 32.00, 32.01, and 32.02 vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.
CVE-2020-12005 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 7.8 HIGH 7.5 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. A vulnerability exists in the communication function that enables users to upload EDS files by FactoryTalk Linx. This may allow an attacker to upload a file with bad compression, consuming all the available CPU resources, leading to a denial-of-service condition.
CVE-2020-12003 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 5.0 MEDIUM 7.5 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to use specially crafted requests to traverse the file system and expose sensitive data on the local hard drive.
CVE-2020-12001 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 7.5 HIGH 9.8 CRITICAL
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. The parsing mechanism that processes certain file types does not provide input sanitation. This may allow an attacker to use specially crafted files to traverse the file system and modify or expose sensitive data or execute arbitrary code.
CVE-2020-11999 1 Rockwellautomation 2 Factorytalk Linx, Rslinx Classic 2024-11-21 5.5 MEDIUM 8.1 HIGH
FactoryTalk Linx versions 6.00, 6.10, and 6.11, RSLinx Classic v4.11.00 and prior,Connected Components Workbench: Version 12 and prior, ControlFLASH: Version 14 and later, ControlFLASH Plus: Version 1 and later, FactoryTalk Asset Centre: Version 9 and later, FactoryTalk Linx CommDTM: Version 1 and later, Studio 5000 Launcher: Version 31 and later Stud, 5000 Logix Designer software: Version 32 and prior is vulnerable. An exposed API call allows users to provide files to be processed without sanitation. This may allow an attacker to specify a filename to execute unauthorized code and modify files or data.
CVE-2020-10642 1 Rockwellautomation 1 Rslinx Classic 2024-11-21 7.2 HIGH 7.8 HIGH
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic.
CVE-2019-6553 1 Rockwellautomation 1 Rslinx 2024-11-21 7.5 HIGH 9.8 CRITICAL
A vulnerability was found in Rockwell Automation RSLinx Classic versions 4.10.00 and prior. An input validation issue in a .dll file of RSLinx Classic where the data in a Forward Open service request is passed to a fixed size buffer, allowing an attacker to exploit a stack-based buffer overflow condition.
CVE-2019-10970 1 Rockwellautomation 2 Panelview 5510, Panelview 5510 Firmware 2024-11-21 10.0 HIGH 9.8 CRITICAL
In Rockwell Automation PanelView 5510 (all versions manufactured before March 13, 2019 that have never been updated to v4.003, v5.002, or later), a remote, unauthenticated threat actor with access to an affected PanelView 5510 Graphic Display, upon successful exploit, may boot-up the terminal and gain root-level access to the device’s file system.
CVE-2019-10955 1 Rockwellautomation 11 Compactlogix 5370 L1, Compactlogix 5370 L1 Firmware, Compactlogix 5370 L2 and 8 more 2024-11-21 5.8 MEDIUM 6.1 MEDIUM
In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine.
CVE-2019-10954 1 Rockwellautomation 10 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 7 more 2024-11-21 7.8 HIGH 7.5 HIGH
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.
CVE-2019-10952 1 Rockwellautomation 8 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compactlogix 5370 L1 and 5 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier.