Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability. This vulnerability allows remote attackers to disclose sensitive information on affected installations of Honeywell Saia PG5 Controls Suite. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file.
The specific flaw exists within the parsing of xml files. Due to the improper restriction of XML External Entity (XXE) references, a crafted document specifying a URI causes the XML parser to access the URI and embed the contents back into the XML document for further processing. An attacker can leverage this vulnerability to disclose information in the context of the current process.
. Was ZDI-CAN-18563.
References
Link | Resource |
---|---|
https://www.zerodayinitiative.com/advisories/ZDI-23-1850/ | Third Party Advisory |
https://www.zerodayinitiative.com/advisories/ZDI-23-1850/ | Third Party Advisory |
Configurations
Configuration 1 (hide)
|
History
12 Mar 2025, 13:45
Type | Values Removed | Values Added |
---|---|---|
CPE | cpe:2.3:a:honeywell:saia_pg5_controls_suite:2.3.193:*:*:*:*:*:*:* cpe:2.3:a:honeywell:saia_pg5_controls_suite:-:*:*:*:*:*:*:* |
|
References | () https://www.zerodayinitiative.com/advisories/ZDI-23-1850/ - Third Party Advisory | |
CVSS |
v2 : v3 : |
v2 : unknown
v3 : 6.5 |
First Time |
Honeywell
Honeywell saia Pg5 Controls Suite |
Information
Published : 2024-05-03 03:16
Updated : 2025-03-12 13:45
NVD link : CVE-2023-51601
Mitre link : CVE-2023-51601
CVE.ORG link : CVE-2023-51601
JSON object : View
Products Affected
honeywell
- saia_pg5_controls_suite
CWE
CWE-611